SILVER AUTOMATION INSTRUMENTS LTD.
Product Category

By Media
Flow Meter

Comprehensive Pressure Transmitter Installation Guide — Electrical Wiring, Mounting, and Calibration


Installing a pressure transmitter correctly is critical to ensure reliable, stable, and accurate pressure, differential pressure, or liquid level measurements in any industrial process.
This detailed guide from Silver Automation Instruments provides step-by-step instructions and best practices for electrical installation, mechanical mounting, impulse line layout, and remote diaphragm seal configuration.
Whether you are setting up a differential pressure transmitter, gauge pressure transmitter, or level transmitter, proper installation guarantees measurement precision, device longevity, and safe operation under demanding industrial conditions.

transmitter/dp transmitter
Transmitter/DP transmitter



1. Electrical Installation and Wiring of Pressure Transmitters

terminal of DP transmitters
Termincal of DP transmitter

Electrical wiring is the foundation for stable signal transmission. The power supply wire and signal wire share the same cable, simplifying installation and reducing potential wiring errors.

To begin, remove the housing cover on the terminal compartment side and connect the positive and negative leads to the corresponding terminals. Silver Automation Instruments recommends using a twisted-pair or shielded cable to minimize electromagnetic interference (EMI) and ensure signal stability, especially in environments with heavy electrical noise such as refineries, chemical plants, or power generation facilities.

  • Recommended wire cross-section: 0.5 mm² ≤ S ≤ 2.5 mm²
  • Shielding and grounding: Always ground the shielding properly to avoid signal drift.
  • Moisture protection: Plug and seal any unused conduit entry to prevent moisture accumulation inside the terminal compartment.
  • Conduit separation: Do not run the signal cable in the same conduit as high-voltage power lines.

If the conduit cannot be sealed, it should face downward (“adown”) to prevent condensation buildup inside the transmitter enclosure.

Proper electrical installation ensures that your pressure transmitter output (4–20mA, pulse, or digital HART/Modbus signal) remains stable and accurate throughout the operating life of the device.

DP Transmitter wiring
DP Transmitter wiring

2. Mechanical Installation and Mounting Methods

 Diaphragm Seal dp transmitter install
Diaphragm Seal DP Transmitter install

Pressure transmitters can be mounted directly on process taps or remotely using brackets and impulse lines. Silver Automation Instruments offers several mounting configurations, including:

  • Bent bracket pipe mounting
  • Bent bracket panel mounting
  • Flat bracket pipe mounting
  • Flat bracket panel mounting
bent bracket mounting
Bent Bracket Pipe Mounting                        Bent Bracket Panel Mounting
Flat Bracket Pipe Mounting                              Flat Bracket Panel Mounting

These configurations allow flexible installation depending on plant layout and accessibility.

2.1 Process Connection and Mounting Tips

The process connection of most transmitters is ¼ NPT on the flange, with adaptors available for ½ NPT taper threads.
When connecting impulse lines, tighten bolts incrementally in a cross pattern to avoid distortion, using a maximum torque of 40 N·m.

Key mechanical recommendations:

  • Keep impulse piping as short and straight as possible.
  • Avoid sudden temperature fluctuations, vibration, or corrosive atmospheres.
  • Mount the pressure capsule vertically to prevent zero shift.
  • For differential pressure transmitters measuring vertical pipelines, compensate for height difference using “zero pressure trim” through the display or HART communicator.

Proper mounting of the pressure transmitter and impulse lines directly affects measurement accuracy and repeatability.


3. Impulse Line Installation and Error Prevention

Impulse lines transfer pressure from the process taps to the transmitter. Incorrect impulse line design or installation can cause measurement drift or systematic errors.

Common Causes of Measurement Errors

  • Leakage or loose fittings
  • Erosion or abrasion due to purge gas or liquid
  • Gas bubbles in liquid lines or liquid slugs in gas lines
  • Unequal temperature across both impulse legs
  • Incorrect slope causing trapped gas or condensate

Best Practices to Minimize Error

  • Keep impulse piping short and equal in length.
  • For liquid service, slope the impulse piping upward (≥1/12) from transmitter to process.
  • For gas service, slope it downward (≥1/12) from transmitter to process.
  • Vent gas from liquid legs and drain condensate from gas legs.
  • Use large-diameter tubing to prevent friction loss and blockage.
  • When purging, connect purge lines near the process taps and purge through equal-length pipes—never purge through the transmitter.
  • Maintain both impulse lines at similar temperature to prevent density differences.

These guidelines are essential for reliable differential pressure measurement and long-term transmitter stability.


4. Remote Diaphragm Seal Installation Guidelines

In applications involving high viscosity, high temperature, or corrosive media, remote diaphragm seal transmitters are used to isolate the sensing element from the process fluid.

Best Installation Practices

  • Keep capillaries as short as possible to reduce response time.
  • Avoid direct sunlight or heat sources to prevent temperature-induced drift.
  • Ensure both capillaries are equal in length when using dual remote seals.
  • Mount transmitters with one diaphragm seal at or below the process connection level.
  • For two remote seals, install the transmitter between or slightly below both seals.
Remote Diaphragm Seal pressure transmitter Installation
Remote Diaphragm Seal pressure transmitter Installation

Correct capillary routing and equal seal lengths ensure stable readings and accurate pressure or level measurement in reactors, tanks, and pipelines.


5. Liquid, Gas, and Steam Flow Measurement

Different media require specific installation orientations to ensure accuracy and prevent trapped phases.

5.1 Liquid Flow Measurement


Liquid Flow Measurement

  • Place taps on the side of the line to prevent sediment accumulation.
  • Mount the transmitter beside or below the taps so gases can vent into the process.
  • Keep the drain/vent valve facing upward to allow gas release.

5.2 Gas Flow Measurement

  • Mount taps on the top or side of the pipeline.
  • Install the transmitter above the taps to allow liquids to drain back into the line.

5.3 Steam Flow Measurement

  • Install taps on the side of the line, and mount the transmitter below the taps to keep the impulse lines filled with condensate.
  • For steam above 250°F (121°C), fill impulse lines with water to protect the sensor and maintain measurement accuracy.
  • Ensure the process temperature does not exceed the transmitter’s rated limit.

These guidelines guarantee accurate flow readings across different media and operating conditions.


6. Level Measurement Using Pressure Transmitters

Pressure transmitters can also be used to measure liquid level in open or closed vessels by detecting the hydrostatic pressure of the liquid column.

6.1 Open Vessels

Connect the transmitter’s high-pressure side to the bottom tap, with the low-pressure side vented to the atmosphere.
If the transmitter and tap are on the same level:


Transmitter with the same level as tap

Px=x×ρ×g

where x = liquid height (m), ρ = fluid density (kg/m³), g = 9.80665 m/s².

Example: For x = 6.5 m and ρ = 1000 kg/m³,
Range = 0 ~ 63.7 kPa.

If the transmitter is higher or lower than the tap, additional terms (±hρ₀g) must be included to correct for height differences and fill fluid density (ρ₀).


Transmitter with higer level than Tap

Transmitter with lower level than Tap

6.2 Closed Vessels

In closed tanks, the transmitter must compensate for vapor or gas pressure above the liquid.
Two main methods are used:

  • Dry leg condition: Gas above liquid does not condense; the low-pressure side remains empty.
  • Wet leg condition: Both sides are filled with liquid using double remote seals to prevent condensation errors.

Example calculation (wet leg):

Range=g(yρhρ0) g[(x+y)ρhρ0]

This ensures the differential pressure reflects only the actual liquid level, not vessel pressure variations.

⚠️ Attention: The process medium should not freeze, or it may damage the isolation diaphragm or transmitter module.


transmitter and DP transmitter install

Transmitter and DP transmitter install

7. Environmental and Safety Considerations

  • Avoid installing transmitters in areas with strong vibration, extreme temperature change, or direct sunlight.
  • Use heating jackets for viscous or heavy oils.
  • For explosion-proof models, ensure compliance with hazardous area certification (ATEX / Exd).
  • Always depressurize and vent lines before maintenance or calibration.

Following these safety and environmental recommendations ensures long-term reliability and compliance with industrial standards.


8. Troubleshooting Common Installation Problems

Problem

Likely Cause

Recommended Solution

Unstable reading

Gas in liquid line / poor grounding

Vent trapped air, check shielding

Zero shift

Horizontal capsule position

Rotate housing, perform zero trim

Slow response

Long or unequal capillaries

Shorten and equalize lines

Drifting signal

Moisture ingress

Seal conduits and dry connections

Incorrect level reading

Temperature difference in legs

Use equal-length impulse lines

Proper preventive maintenance and installation checks can eliminate most issues encountered during field commissioning.


9. Why Choose Silver Automation Instruments

Silver Automation Instruments is a trusted pressure transmitter manufacturer in China, serving global customers across industries such as oil & gas, power generation, water treatment, and chemical processing.

We provide:

  • Differential, gauge, and absolute pressure transmitters
  • Models with remote diaphragm seals, HART/Modbus output, and explosion-proof housing
  • Factory calibration and full ISO 9001 compliance
  • Custom process connections and materials for corrosive applications

Visit our website www.silverinstruments.com to explore our full range of industrial automation instruments, including Coriolis mass flow meters, magnetic flow meters, and positive displacement flow meters.


Conclusion

Proper pressure transmitter installation and wiring is vital for obtaining accurate process data and maintaining plant efficiency.
By following the electrical, mechanical, and calibration recommendations provided by Silver Automation Instruments, you can ensure your transmitter performs reliably under all conditions — whether measuring steam flow, tank level, or process pressure.

With careful attention to details like impulse line routing, capillary placement, and environmental protection, your transmitter will deliver years of precise, maintenance-free service.


FAQs: Pressure Transmitter Installation, Wiring & Calibration

1) What cable should I use for a 4–20 mA/HART pressure transmitter?

Use twisted-pair, shielded cable (0.5–2.5 mm²). Ground the shield at one end only (typically the control room) to reduce ground loops and EMI.

2) Can I route the transmitter signal cable in the same conduit as power lines?

No. Run low-level signal wiring in a separate conduit. If a conduit entry can’t be sealed, orient it downward to prevent moisture ingress.

3) How do I prevent moisture from causing drift or intermittent signals?

Seal unused entries, use proper cable glands, add a drip loop, and consider a desiccant pack in humid areas. Inspect periodically for condensation.

4) What straight-run and mounting orientation help minimize zero shift?

Mount the capsule vertical when possible. For DP applications, keep impulse lines short, equal in length, and correctly sloped (liquid: up toward process; gas: down toward process).

5) When should I choose a wet leg vs. a dry leg for closed vessels?

Dry leg: Vapor space is non-condensing (stays dry).
Wet leg: Vapor condenses or temperatures vary; fill both legs (or use dual remote seals) to keep densities stable and avoid level errors.

6) How do I size capillaries for remote diaphragm seals?

Keep them as short as practical, protected from heat/sun, and equal length for dual seals. Shorter and equal capillaries improve response and reduce temperature-induced drift.

7) What torque should I apply to process connections and flanges?

Tighten bolts gradually with a cross pattern; maximum typical torque is 40 N·m for the listed assemblies (verify with your specific model and gasket material).

8) How do I zero and range a DP transmitter after installation?

Isolate the process, equalize both sides (open equalizing valve), perform zero trim from the display or HART/Field communicator, then apply a known pressure (hand pump or deadweight) to set span.

9) What are common causes of unstable readings and how do I fix them?

Air in liquid legs, liquid slugs in gas legs, loose fittings, poor shielding/grounding, and temperature differences between impulse lines. Vent/drain legs, tighten fittings, and equalize line lengths and temperatures.

10) How should I install taps for liquid, gas, and steam flow measurement?

Liquid: taps on the side; transmitter at/below taps so gases vent to process.
Gas: taps on top/side; transmitter above taps so liquids drain back.
Steam: taps on the side; transmitter below taps; fill legs with water above 121 °C to protect the sensor.

11) What safety and certification points matter in hazardous areas?

Use transmitters with appropriate approvals (e.g., ATEX/IECEx Ex d/Ex ia). Ensure proper barriers, grounding, and installation per the zone classification and local code.

12) How do I calculate the range for level measurement in open tanks?

Range ≈ ρ·g·H (e.g., 1000 kg/m³ × 9.80665 m/s² × height). If the transmitter is not at the same elevation as the bottom tap, include head corrections from elevation differences and any fill fluid.

13) Why is my response time slow on a remote seal system?

Excessive capillary length, small bore, or temperature gradients increase fill-fluid viscosity and response time. Shorten/equalize capillaries and insulate from heat sources.

14) How often should a pressure transmitter be calibrated?

Typical plant practice is 6–12 months. Calibrate sooner after first startup, after maintenance, or when process or ambient conditions change significantly.

15) What’s the best way to purge impulse lines without damaging the transmitter?

Introduce purge near the process taps and purge through equal-length tubing back to process or a safe drain—never purge through the transmitter body.


Author: Silver Automation Instruments — Engineering Team

Practical instrumentation specialists with 10+ years of field experience in flow, pressure, and level measurement. Expertise in Pressure, gas turbine, Coriolis, magnetic, and ultrasonic meters. ISO 9001 processes.

Website: |  Email: technician@silverinstruments.com


Email
WhatsApp
Inquiry